Example of actual NSA results
in a TDK 3 meter test range CISPR semi anechoic chamber
(measured by ARC Seibersdorf).

Chamber Specifications
Dimensions:
9.0 m long x 6.0 m wide x 5.4 m high (29'-6" L x 19'-8" W x 17'-8" H)
Absorbers: IB-015
fully lined double layer ferrite
tile IP-045C partially lined absorber
NSA test volume ±3.5dB (@3m):
2.0 m Ø, 2.0 m high
Field uniformity area (-0, +6dB):
1.5 x 1.5 m, 0.8 m from floor
Radiated emissions:
Compliance with ANSI C63.4, EN
50147-2, CISPR 22
Radiated immunity:
Compliance with IEC 1000-4-3
EMI frequency range:
30 MHz - 18 GHz
EMS frequency range: 26 MHz - 18 GHz
____________________________________________________________________________________________
To place an order or to learn more about the TDK RF Solutions products
that best meet your needs, contact your TDK RF Solutions sales
representative:
TDK RF Solutions Inc.
1101 Cypress Creek Rd.
Cedar Park, Texas 78613 USA
Phone:
+1 (512) 258-9478
Fax: +1 (512) 258-0740
E-mail: info@tdkrf.com
Specifications subject to change without
notice.
|